Перевод: со всех языков на все языки

со всех языков на все языки

(длительный) допустимый ток

  • 1 длительный допустимый ток

    1. Strombelastbarkeit, f
    2. Dauerstrombelastbarkeit, f

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Русско-немецкий словарь нормативно-технической терминологии > длительный допустимый ток

  • 2 длительный допустимый ток

    1. current-carrying capacity
    2. continuous current-carrying capacity
    3. continuous current
    4. ampacity (US)

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Русско-английский словарь нормативно-технической терминологии > длительный допустимый ток

  • 3 длительный допустимый ток

    1. courant permanent admissible, m
    2. courant admissible, m

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Русско-французский словарь нормативно-технической терминологии > длительный допустимый ток

  • 4 допустимый длительный ток кабеля (провода)

    1. current-carrying capacity of the cable
    2. current carrying capacity of the conductors
    3. current carrying capacity of the cable
    4. current carrying capacity
    5. ampere capacity

     

    допустимый длительный ток кабеля (провода)
    -
    [Интент]

    допустимый длительный ток (проводника)
    Максимальный электрический ток, который проводник способен проводить в продолжительном режиме без превышения его установившейся температурой определённого значения.
    Допустимый длительный ток является одной из основных характеристик проводника. Он представляет собой максимальный электрический ток, который проводник может проводить длительно (неделями, месяцами, годами) не перегреваясь. Значение допустимого длительного тока зависит от сечения проводника, материалов из которых выполнены проводник и его изоляция, способов монтажа проводника в электроустановке здания. Допустимый длительный ток проводника фактически является его номинальным током. В электроустановках зданий выполняют защиту проводников от сверхтоков, протекание которых по проводникам сопровождается их перегревом.
    [ http://www.volt-m.ru/glossary/letter/%C4/view/11/]

    EN

    current carrying capacity
    maximum current a cable circuit (one or several conductors) can support resulting in a specified increase of the surface temperature of the conductor beyond the ambient temperature, not exceeding the maximum allowed operating temperature of the cable
    [IEC 61156-1, ed. 3.0 (2007-06< size="2">)]

    FR

    courant maximal admissible
    courant maximal qu’un circuit de câble (un ou plusieurs conducteurs) peut supporter avec une augmentation spécifiée de la température de surface du conducteur au delà de la température ambiante, et ne dépassant pas la température maximale de fonctionnement autorisée du câble
    [IEC 61156-1, ed. 3.0 (2007-06< size="2">)]

    Номинальный ток устройств защиты от короткого замыкания может превышать допустимый длительный ток кабеля.
    [ ГОСТ Р 50571. 5-94 ( МЭК 364-4-43-77)]

    Допустимые длительные токи для проводов и кабелей, проложенных в коробах, а также в лотках пучками, должны приниматься...
    [ПУЭ]

    Тематики

    EN

    FR

    Русско-английский словарь нормативно-технической терминологии > допустимый длительный ток кабеля (провода)

  • 5 допустимый длительный ток кабеля (провода)

    1. courant maximal admissible

     

    допустимый длительный ток кабеля (провода)
    -
    [Интент]

    допустимый длительный ток (проводника)
    Максимальный электрический ток, который проводник способен проводить в продолжительном режиме без превышения его установившейся температурой определённого значения.
    Допустимый длительный ток является одной из основных характеристик проводника. Он представляет собой максимальный электрический ток, который проводник может проводить длительно (неделями, месяцами, годами) не перегреваясь. Значение допустимого длительного тока зависит от сечения проводника, материалов из которых выполнены проводник и его изоляция, способов монтажа проводника в электроустановке здания. Допустимый длительный ток проводника фактически является его номинальным током. В электроустановках зданий выполняют защиту проводников от сверхтоков, протекание которых по проводникам сопровождается их перегревом.
    [ http://www.volt-m.ru/glossary/letter/%C4/view/11/]

    EN

    current carrying capacity
    maximum current a cable circuit (one or several conductors) can support resulting in a specified increase of the surface temperature of the conductor beyond the ambient temperature, not exceeding the maximum allowed operating temperature of the cable
    [IEC 61156-1, ed. 3.0 (2007-06< size="2">)]

    FR

    courant maximal admissible
    courant maximal qu’un circuit de câble (un ou plusieurs conducteurs) peut supporter avec une augmentation spécifiée de la température de surface du conducteur au delà de la température ambiante, et ne dépassant pas la température maximale de fonctionnement autorisée du câble
    [IEC 61156-1, ed. 3.0 (2007-06< size="2">)]

    Номинальный ток устройств защиты от короткого замыкания может превышать допустимый длительный ток кабеля.
    [ ГОСТ Р 50571. 5-94 ( МЭК 364-4-43-77)]

    Допустимые длительные токи для проводов и кабелей, проложенных в коробах, а также в лотках пучками, должны приниматься...
    [ПУЭ]

    Тематики

    EN

    FR

    Русско-французский словарь нормативно-технической терминологии > допустимый длительный ток кабеля (провода)

  • 6 courant admissible, m

    1. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Франко-русский словарь нормативно-технической терминологии > courant admissible, m

  • 7 courant permanent admissible, m

    1. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Франко-русский словарь нормативно-технической терминологии > courant permanent admissible, m

  • 8 Dauerstrombelastbarkeit, f

    1. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Немецко-русский словарь нормативно-технической терминологии > Dauerstrombelastbarkeit, f

  • 9 Strombelastbarkeit, f

    1. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Немецко-русский словарь нормативно-технической терминологии > Strombelastbarkeit, f

  • 10 continuous current-carrying capacity

    1. длительный допустимый ток
    2. длительная пропускная способность по току

     

    длительная пропускная способность по току

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Англо-русский словарь нормативно-технической терминологии > continuous current-carrying capacity

  • 11 ampacity (US)

    1. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Англо-русский словарь нормативно-технической терминологии > ampacity (US)

  • 12 current-carrying capacity

    1. прочность печатной платы к токовой нагрузке
    2. предельно допустимый ток
    3. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

     

    предельно допустимый ток

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    прочность печатной платы к токовой нагрузке
    Свойство печатной платы сохранять электрические и механические характеристики после воздействия максимально допустимой токовой нагрузки на печатный проводник или металлизированное отверстие печатной платы.
    [ ГОСТ Р 53386-2009]

    Тематики

    EN

    Англо-русский словарь нормативно-технической терминологии > current-carrying capacity

  • 13 continuous current

    1. непрерывный ток
    2. длительный допустимый ток

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

     

    непрерывный ток

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999]

    Тематики

    • электротехника, основные понятия

    EN

    Англо-русский словарь нормативно-технической терминологии > continuous current

  • 14 fault

    1. ток повреждения
    2. сверхток
    3. сброс
    4. сбой
    5. разлом
    6. повреждение (цепи, линии, устройства)
    7. повреждение (во взрывозащите)
    8. повреждение
    9. ошибка
    10. отказ
    11. ненормальный режим работы
    12. неисправность
    13. неисправное состояние
    14. нарушение
    15. короткое замыкание
    16. дизъюктивное нарушение
    17. дефект
    18. выход из строя
    19. аварийное сообщение

     

    аварийное сообщение
    -

    Параллельные тексты EN-RU

    The system offers diagnostic and statistics functions and configurable warnings and faults, allowing better prediction of component maintenance, and provides data to continuously improve the entire system.
    [Schneider Electric]

    Система (управления электродвигателем) предоставляет оператору различную диагностическую и статистическую информацию и позволяет сконфигурировать предупредительные и аварийные сообщения, что дает возможность лучше планировать техническое обслуживание и постоянно улучшать систему в целом.
    [Перевод Интент]

    Various alarm notifications are available to indicate a compromised security state such as forced entry and door position.
    [APC]

    Устройство может формировать различные аварийные сообщения о нарушении защиты, например, о несанкционированном проникновении или об изменении положения двери.
    [Перевод Интент]


    Тематики

    EN

     

    выход из строя

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    выход системы из строя
    вследствие отказа аппаратного или программного обеспечения либо средств связи
    [Англо-русский толковый словарь терминов и сокращений по ВТ, Интернету и программированию. © 1998-2007 гг., Э.М. Пройдаков, Л.А. Теплицкий. 13,8 тыс. статей.]

    выход из строя
    -

    [Интент]

    Единичные выходы из строя в процессе испытаний элементов электронной техники (микросхем, электровакуумных и полупроводниковых приборов, конденсаторов, резисторов, кварцевых резонаторов и т.д.), а также ламп накаливания и предохранителей не могут служить основанием для прекращения испытаний, если это не вызвано недостатком конструкции прибора.

    При повторных выходах из строя тех же элементов испытания следует считать неудовлетворительными.
    [ ГОСТ 24314-80]

    При выходе из строя отдельно стоящих вентиляторов на двигателях мельниц, дымососов, мельничных вентиляторов, вентиляторов первичного воздуха и т.д. необходимо при первой возможности, но не позже чем его допускается заводской инструкцией, отключить двигатель 6 кВ для ремонта вентилятора охлаждения двигателя.
    [РД 34.20.565]

    Судовая электрическая сеть, предназначенная для передачи электроэнергии при выходе из строя линий электропередачи силовой сети или исчезновении напряжения
    [ ГОСТ 22652-77]

    Тематики

    Синонимы

    EN

     

    дизъюктивное нарушение
    Относительное перемещение частей пластов вдоль плоскости их разрыва (геол.)
    [ http://slovarionline.ru/anglo_russkiy_slovar_neftegazovoy_promyishlennosti/]

    Тематики

    EN

     

    короткое замыкание
    Случайное или намеренное соединение резистором или импедансом со сравнительно низким сопротивлением двух или более точек в цепи, нормально находящихся под различным напряжением.
    Случайное или намеренное низкоимпедансное или низкоомное соединение двух или более точек электрической цепи, нормально находящихся под разными электрическими потенциалами. (вариант компании Интент)
    МЭК 60050(151-03-41) [2].
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]

    короткое замыкание
    Случайный или преднамеренный проводящий путь между двумя или более проводящими частями, принуждающий различия электрических потенциалов между этими проводящими частями становиться равными или близкими к нулю.
    Короткое замыкание обычно возникает в аварийном режиме электроустановки здания при повреждении изоляции токоведущих частей, находящихся под разными электрическими потенциалами, и возникновении между этими частями электрического контакта, имеющего пренебрежимо малое полное сопротивление. Короткое замыкание также может быть следствием ошибочных действий, совершаемых персоналом при монтаже и эксплуатации электроустановки здания, когда соединяют между собой проводящие части, которые в нормальном режиме находятся под разными электрическими потенциалами.
    Короткое замыкание характеризуется током короткого замыкания, который, многократно превышая номинальный ток электрической цепи, может вызвать возгорание её элементов и явиться причиной пожара в здании. Поэтому в электроустановках зданий всегда проводят мероприятия, направленные на снижение вероятности возникновения короткого замыкания, а также выполняют защиту от короткого замыкания с помощью устройств защиты от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%CA/view/27/]

    короткое замыкание
    Случайное или преднамеренное соединение двух или более проводящих частей, вызывающее снижение разности электрических потенциалов между этими частями до нуля или значения, близкого к нулю.
    [ ГОСТ Р МЭК 60050-195-2005]

    короткое замыкание
    КЗ

    замыкание, при котором токи в ветвях электроустановки, примыкающих к месту его возникновения, резко возрастают, превышая наибольший допустимый ток продолжительного режима
    [Методические указания по защите распределительных электрических сетей напряжением 0,4-10 кВ от грозовых перенапряжений]

    EN

    short-circuit
    accidental or intentional conductive path between two or more conductive parts forcing the electric potential differences between these conductive parts to be equal to or close to zero
    Source: 151-03-41 MOD
    [IEV number 195-04-11]

    FR

    court-circuit
    chemin conducteur accidentel ou intentionnel entre deux ou plusieurs parties conductrices forçant les différences de potentiel électriques entre ces parties conductrices à être nulles ou proches de zéro
    Source: 151-03-41 MOD
    [IEV number 195-04-11]

    Параллельные тексты EN-RU

    A short-circuit is a low impedance connection between two conductors at different voltages.
    [ABB]

    Короткое замыкание представляет собой низкоомное соединение двух проводников, находящихся под разными потенциалами.
    [Перевод Интент]

    Тематики

    Синонимы

    • КЗ

    EN

    DE

    FR

     

    нарушение
    [Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]

    EN

    fault
    Another term for offense.
    [Департамент лингвистических услуг Оргкомитета «Сочи 2014». Глоссарий терминов]

    Тематики

    EN

     

    неисправное состояние
    Состояние объекта, при котором он не соответствует хотя бы одному из требований нормативно-технической и (или) конструкторской (проектной) документации.
    [ ГОСТ 27.002-89]
    [ОСТ 45.152-99]

    неисправное состояние
    неисправность

    По ГОСТ 13377-75
    [ ГОСТ 24166-80]

    неисправное состояние
    Состояние системы тревожной сигнализации, препятствующее реагированию системы на наличие опасности в соответствии с требованиями стандартов.
    [ ГОСТ Р 50775-95]
    [МЭК 839-1-1-88]

    Тематики

    Обобщающие термины

    Синонимы

    EN

    DE

    FR

     

    неисправность
    отказ в работе

    Состояние машины, характеризующееся неспособностью выполнять заданную функцию, исключая случаи проведения профилактического технического обслуживания, других запланированных действий или недостаток внешних ресурсов (например, отключение энергоснабжения).
    Примечание 1
    Неисправность часто является результатом повреждения самой машины, однако она может иметь место и без повреждения.
    Примечание 2
    На практике термины «неисправность», «отказ» и «повреждение» часто используются как синонимы.
    [ ГОСТ Р ИСО 12100-1:2007]

    неисправность

    Состояние оборудования, характеризуемое его неспособностью выполнять требуемую функцию, исключая профилактическое обслуживание или другие планово-предупредительные действия, а также исключая неспособность выполнять требуемую функцию из-за недостатка внешних ресурсов.
    Примечание - Неисправность часто является следствием отказа самого оборудования, но может существовать и без предварительного отказа.
    [ГОСТ ЕН 1070-2003]

    неисправность
    Состояние технического объекта (элемента), характеризуемое его неспособностью выполнять требуемую функцию, исключая периоды профилактического технического обслуживания или другие планово-предупредительные действия, или в результате недостатка внешних ресурсов.
    Примечания
    1 Неисправность является часто следствием отказа самого технического объекта, но может существовать и без предварительного отказа.
    2 Английский термин «fault» и его определение идентичны данному в МЭК 60050-191 (МЭС 191-05-01) [1]. В машиностроении чаще применяют французский термин «defaut» или немецкий термин «Fehler», чем термины «panne» и «Fehlzusstand», которые употребляют с этим определением.
    [ ГОСТ Р ИСО 13849-1-2003]

    Тематики

    EN

    DE

    FR

     

    ненормальный режим работы электротехнического изделия
    Режим работы электротехнического изделия (электротехнического устройства, электрооборудования), при котором значение хотя бы одного из параметров режима выходит за пределы наибольшего или наименьшего рабочего значения.
    [ ГОСТ 18311-80]


    К ненормальным относятся режимы, связанные с отклонениями от допустимых значений величин тока, напряжения и частоты, опасные для оборудования или устойчивой работы энергосистемы.

    Рассмотрим наиболее характерные ненормальные режимы.

    а) Перегрузка оборудования, вызванная увеличением тока сверх номинального значения. Номинальным называется максимальный ток, допускаемый для данного оборудования в течение неограниченного времени.
    Если ток, проходящий по оборудованию, превышает номинальное значение, то за счет выделяемого им дополнительного тепла температура токоведущих частей и изоляции через некоторое время превосходит допустимую величину, что приводит к ускоренному износу изоляции и ее повреждению. Время, допустимое для прохождения повышенных токов, зависит от их величины. Характер этой зависимости показан на рис. 1-3 и определяется конструкцией оборудования и типом изоляционных материалов. Для предупреждения повреждения оборудования при его перегрузке необходимо принять меры к разгрузке или отключению оборудования.

    б) Качания в системах возникают при выходе из синхронизма работающих параллельно генераторов (или электростанций) А и В (рис. 1-2, б). При качаниях в каждой точке системы происходит периодическое изменение («качание») тока и напряжения. Ток во всех элементах сети, связывающих вышедшие из синхронизма генераторы А и В, колеблется от нуля до максимального значения, во много раз превышающего нормальную величину. Напряжение падает от нормального до некоторого минимального значения, имеющего разную величину в каждой точке сети. В точке С, называемой электрическим центром качаний, оно снижается до нуля, в остальных точках сети напряжение падает, но остается больше нуля, нарастая от центра качания С к источникам питания А и В. По характеру изменения тока и напряжения качания похожи на к. з. Возрастание тока вызывает нагревание оборудования, а уменьшение напряжения нарушает работу всех потребителей системы. Качание — очень опасный ненормальный режим, отражающийся на работе всей энергосистемы.

    в) Повышение напряжения сверх допустимого значения возникает обычно на гидрогенераторах при внезапном отключении их нагрузки. Разгрузившийся гидрогенератор увеличивает частоту вращения, что вызывает возрастание э. д. с. статора до опасных для его изоляции значений. Защита в таких случаях должна снизить ток возбуждения генератора или отключить его.
    Опасное для изоляции оборудования повышение напряжения может возникнуть также при одностороннем отключении или включении длинных линий электропередачи с большой емкостной проводимостью.
    Кроме отмеченных ненормальных режимов, имеются и другие, ликвидация которых возможна при помощи релейной защиты.

    [Чернобровов Н. В. Релейная защита. Учебное пособие для техникумов]

    Тематики

    Синонимы

    EN

     

    отказ
    Нарушение способности оборудования выполнять требуемую функцию.
    Примечания
    1. После отказа оборудование находится в неисправном состоянии.
    2. «Отказ» является событием, в отличие от «неисправности», которая является состоянием.
    3. Это понятие, как оно определено, не применяют к оборудованию объекту, состоящему только из программных средств.
    4. На практике термины «отказ» и «неисправность» часто используют как синонимы.
    [ГОСТ ЕН 1070-2003]
    [ ГОСТ Р ИСО 13849-1-2003]
    [ ГОСТ Р МЭК 60204-1-2007]

    отказ
    Событие, заключающееся в нарушении работоспособного состояния объекта.
    [ ГОСТ 27.002-89]
    [ОСТ 45.153-99]
    [СТО Газпром РД 2.5-141-2005]
    [СО 34.21.307-2005]

    отказ
    Событие, заключающееся в нарушении работоспособного состояния машины и (или) оборудования вследствие конструктивных нарушений при проектировании, несоблюдения установленного процесса производства или ремонта, невыполнения правил или инструкций по эксплуатации.
    [Технический регламент о безопасности машин и оборудования]

    EN

    failure
    the termination of the ability of an item to perform a required function
    NOTE 1 – After failure the item has a fault.
    NOTE 2 – "Failure" is an event, as distinguished from "fault", which is a state.
    NOTE 3 – This concept as defined does not apply to items consisting of software only.
    [IEV number 191-04-01]
    NOTE 4 - In practice, the terms fault and failure are often used synonymously
    [IEC 60204-1-2006]

    FR

    défaillance
    cessation de l'aptitude d'une entité à accomplir une fonction requise
    NOTE 1 – Après défaillance d'une entité, cette entité est en état de panne.
    NOTE 2 – Une défaillance est un passage d'un état à un autre, par opposition à une panne, qui est un état.
    NOTE 3 – La notion de défaillance, telle qu'elle est définie, ne s'applique pas à une entité constituée seulement de logiciel.
    [IEV number 191-04-01]

    Тематики

    Обобщающие термины

    EN

    DE

    FR

     

    повреждение
    Повреждение любого элемента, разделения, изоляции или соединения между элементами, не являющихся неповреждаемыми по МЭК 60079-11 [8], при проведении испытаний на искробезопасность.
    [ ГОСТ Р МЭК 60050-426-2006]


    Тематики

    EN

     

    повреждение (цепи, линии, устройства)
    -

    [Интент]

    Тематики

    EN

     

    разлом

    [ http://www.eionet.europa.eu/gemet/alphabetic?langcode=en]

    EN

    fault
    A fracture or a zone of fractures along which there has been displacement of the sides relative to one another parallel to the fracture. (Source: BJGEO)
    [http://www.eionet.europa.eu/gemet/alphabetic?langcode=en]

    Тематики

    EN

    DE

    FR

     

    сбой
    Самоустраняющийся отказ или однократный отказ, устраняемый незначительным вмешательством оператора.
    [ ГОСТ 27.002-89]
    [ОСТ 45.153-99]
    [СТО Газпром РД 2.5-141-2005]

    сбой
    Ненормальный режим, который может вызвать уменьшение или потерю способности функционального блока выполнять требуемую функцию.
    Примечание
    МЭС 191-05-01 определяет «сбой» как состояние, характеризуемое неспособностью выполнить необходимую функцию, исключая неспособности, возникающие во время профилактического ухода или других плановых мероприятий, либо в результате недостатка внешних ресурсов. Иллюстрация к этим двум точкам зрения показана на рисунке [ ИСО / МЭК 2382-14-01-10].
    3743
    [ ГОСТ Р МЭК 61508-4-2007]

    Тематики

    Обобщающие термины

    EN

     

    сброс
    Разрывное нарушение, при котором сместитель падает в сторону опущенного крыла (висячее крыло опущено относительно лежачего).
    [ Словарь геологических терминов и понятий. Томский Государственный Университет]

    Тематики

    • геология, геофизика

    Обобщающие термины

    EN

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

     

    ток повреждения
    Ток, возникающий в результате пробоя или перекрытия изоляции.
    [ ГОСТ Р 51321. 1-2000 ( МЭК 60439-1-92)]

    ток повреждения
    Ток, который протекает через данную точку повреждения в результате повреждения изоляции.
    [ ГОСТ Р МЭК 60050-826-2009]

    EN

    fault current
    current resulting from an insulation failure, the bridging of insulation or incorrect connection in an electrical circuit
    [IEC 61439-1, ed. 2.0 (2011-08)]

    fault current

    current which flows across a given point of fault resulting from an insulation fault
    [IEV number 826-11-11]

    FR

    courant de défaut
    courant résultant d'un défaut de l'isolation, du contournement de l’isolation ou d’un raccordement incorrect dans un circuit électrique
    [IEC 61439-1, ed. 2.0 (2011-08)]

    courant de défaut, m

    courant s'écoulant en un point de défaut donné, consécutivement à un défaut de l'isolation
    [IEV number 826-11-11]

    Тематики

    EN

    DE

    • Fehlerstrom, m

    FR

    • courant de défaut, m

    3.7.2 повреждение (fault): Повреждение любого элемента, разделения, изоляции или соединения между элементами, не являющимися по настоящему стандарту не повреждаемыми, от которых зависит искробезопасность цепи.

    Источник: ГОСТ Р 52350.11-2005: Электрооборудование для взрывоопасных газовых сред. Часть 11. Искробезопасная электрическая цепь "I" оригинал документа

    3.16 неисправность (fault): Состояние объекта, характеризующееся неспособностью исполнять требуемую функцию, исключая время профилактического технического обслуживания или других запланированных действий, или простои из-за недостатка внешних ресурсов

    Примечание - Неисправность часто является результатом отказа объекта, но может существовать и без отказа.

    Источник: ГОСТ Р 51901.6-2005: Менеджмент риска. Программа повышения надежности оригинал документа

    3.6 неисправность (fault): Состояние элемента, характеризующееся неспособностью исполнять требуемую функцию, исключая период технического обслуживания, ремонта или других запланированных действий, а также из-за недостатка внешних ресурсов.

    Примечание - Неисправность часто является результатом отказа элемента, но может существовать и без предшествующего отказа.

    Источник: ГОСТ Р 51901.5-2005: Менеджмент риска. Руководство по применению методов анализа надежности оригинал документа

    3.5 неисправность (fault): Состояние объекта, когда один из его элементов или группа элементов проявляют признаки деградации или нарушения работы, что может привести к отказу машины.

    Примечания

    1 Неисправность часто является следствием отказа, но может иметь место и при его отсутствии.

    2 Состояние объекта не рассматривают как неисправное, если оно возникло вследствие запланированных процедур или нехватки внешних ресурсов.

    Источник: ГОСТ Р ИСО 13379-2009: Контроль состояния и диагностика машин. Руководство по интерпретации данных и методам диагностирования оригинал документа

    3.3 неисправность (fault): Состояние объекта, при котором он не способен выполнять требуемую функцию, за исключением такой неспособности при техническом обслуживании или других плановых мероприятиях или вследствие нехватки внешних ресурсов.

    Примечания

    1 Неисправность часто является следствием отказа объекта, но может иметь место и без него.

    2 В настоящем стандарте термин «неисправность» используется наряду с термином «отказ» по историческим причинам.

    Источник: ГОСТ Р 51901.12-2007: Менеджмент риска. Метод анализа видов и последствий отказов оригинал документа

    3.1.30 ошибка (fault): Разность между погрешностью весоизмерительного датчика и основной погрешностью весоизмерительного датчика (см. 3.1.34).

    Источник: ГОСТ Р 8.726-2010: Государственная система обеспечения единства измерений. Датчики весоизмерительные. Общие технические требования. Методы испытаний оригинал документа

    3.6 дефект (fault): Неисправность или ошибка в компоненте технического обеспечения, программного обеспечения или системы

    [МЭК 61513, пункт 3.22]

    Примечание 1 - Дефекты могут подразделяться на случайные, например, в результате ухудшения аппаратных средств из-за старения, и систематические, например, ошибки в программном обеспечении, которые вытекают из погрешностей проектирования.

    Примечание 2 - Дефект (в особенности дефект проекта) может остаться необнаруженным в системе до тех пор, пока не окажется, что полученный результат не соответствует намеченной функции, то есть возникает отказ.

    Примечание 3 - См. также «ошибка программного обеспечения» и «случайный дефект».

    Источник: ГОСТ Р МЭК 62340-2011: Атомные станции. Системы контроля и управления, важные для безопасности. Требования по предотвращению отказов по общей причине оригинал документа

    3.2 неисправность (fault): Состояние объекта, когда один из его элементов или группа элементов проявляет признаки деградации или нарушения работы, что может привести к отказу машины.

    Примечание - Неисправность может привести к отказу.

    Источник: ГОСТ Р ИСО 17359-2009: Контроль состояния и диагностика машин. Общее руководство по организации контроля состояния и диагностирования оригинал документа

    3.17 дефект (fault): Неисправность или ошибка в компоненте технического обеспечения, программного обеспечения или системы.

    [МЭК 61513, пункт 3.22]

    Источник: ГОСТ Р МЭК 60880-2010: Атомные электростанции. Системы контроля и управления, важные для безопасности. Программное обеспечение компьютерных систем, выполняющих функции категории А оригинал документа

    3.6.1 сбой (fault): Ненормальный режим, который может вызвать уменьшение или потерю способности функционального блока выполнять требуемую функцию.

    Примечание - МЭС 191-05-01 определяет «сбой» как состояние, характеризуемое неспособностью выполнить необходимую функцию, исключая неспособности, возникающие во время профилактического ухода или других плановых мероприятий, либо в результате недостатка внешних ресурсов. Иллюстрация к этим двум точкам зрения показана на рисунке 4 [ИСО/МЭК 2382-14-01-10].

    Источник: ГОСТ Р МЭК 61508-4-2007: Функциональная безопасность систем электрических, электронных, программируемых электронных, связанных с безопасностью. Часть 4. Термины и определения оригинал документа

    3.22 дефект (fault): Дефект в аппаратуре, программном обеспечении или в компоненте системы (см. рисунок 3).

    Примечание 1 -Дефекты могут быть результатом случайных отказов, которые возникают, например, из-за деградации аппаратуры в результате старения; возможны систематические дефекты, например, в результате дефектов в программном обеспечении, возникающих из-за ошибок при проектировании.

    Примечание 2 - Дефект (особенно дефекты, связанные с проектированием) может оставаться незамеченным, пока сохраняются условия, при которых он не отражается на выполнении функции, т.е. пока не произойдет отказ.

    Примечание 3 - См. также «дефект программного обеспечения».

    Источник: ГОСТ Р МЭК 61513-2011: Атомные станции. Системы контроля и управления, важные для безопасности. Общие требования оригинал документа

    4.10.1 ошибка (fault): Разность между погрешностью показаний и погрешностью прибора.

    Источник: ГОСТ Р ЕН 1434-1-2011: Теплосчетчики. Часть 1. Общие требования

    Англо-русский словарь нормативно-технической терминологии > fault

  • 15 сверхток

    1. Überstrom(stärke)
    2. Überstrom

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    Русско-немецкий словарь нормативно-технической терминологии > сверхток

  • 16 surintensité

    1. сверхток

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > surintensité

  • 17 Überstrom

    1. сверхток

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    Немецко-русский словарь нормативно-технической терминологии > Überstrom

  • 18 Überstrom(stärke)

    1. сверхток

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    Немецко-русский словарь нормативно-технической терминологии > Überstrom(stärke)

  • 19 сверхток

    1. surge current
    2. over-current
    3. fault
    4. -

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    3.17. Сверхток - ток, значение которого превосходит наибольшее рабочее значение тока электроустановки.

    Источник: ГОСТ Р 50571.1-93: Электроустановки зданий. Основные положения оригинал документа

    3.17 Сверхток - ток, значение которого превосходит наибольшее рабочее значение тока электроустановки.

    Источник: ГОСТ 30331.1-95: Электроустановки зданий. Основные положения оригинал документа

    3.1.1 сверхток (over-current): Ток, превышающий номинальное значение. [МЭК 60050(441-11-06)] [1]

    Источник: ГОСТ Р 51731-2010: Контакторы электромеханические бытового и аналогичного назначения оригинал документа

    Русско-английский словарь нормативно-технической терминологии > сверхток

  • 20 сверхток

    1. surintensité

     

    сверхток
    Любой ток, превышающий номинальный
    МЭК 60050(441-11-06).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    [ ГОСТ Р 50345-99( МЭК 60898-95)]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Сверхток представляет собой любой электрический ток, величина которого превышает номинальный ток какого-либо элемента электроустановки здания или используемого в ней электрооборудования, например: номинальный ток электрической цепи, допустимый длительный ток проводника, номинальный ток автоматического выключателя и т. д. В нормативной и правовой документации различают два основных вида сверхтока – ток перегрузки и ток короткого замыкания.
    Появление сверхтока в каком-либо элементе электроустановки здания может привести к его перегреву, возгоранию и, как следствие, к возникновению пожара в здании. Поэтому в электроустановках зданий выполняют защиту от сверхтока.
    [ http://www.volt-m.ru/glossary/letter/%D1/view/59/]

    сверхток
    сверхток в электротехническом изделии
    Ток, значение которого превосходит наибольшее рабочее значение тока электротехнического изделия (устройства).
    [ ГОСТ 18311-80]

    сверхток
    Электрический ток, превышающий номинальный электрический ток.
    Примечание - Для проводников номинальный ток считается равным длительному допустимому току.
    [ ГОСТ Р МЭК 60050-826-2009]

    Сверхток может оказывать или может не оказывать вредные воздействия в зависимости от его величины и продолжительности. Сверхтоки могут возникать в результате перегрузок в электроприемниках или при повреждениях, таких как короткие замыкания или замыканиях на землю
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    сверхток
    Любой ток, превышающий номинальное значение. Для проводов номинальным значением является допустимый ток.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    overcurrent
    electric current exceeding the rated electric current
    NOTE – For conductors, the rated current is considered as equal to the current-carrying capacity
    [IEV number 826-11-14]


    over-current
    <>current exceeding the rated current
    <>[IEC 61095, ed. 2.0 (2009-02)]


    over-current
    electric current the value of which exceeds a specified limiting value
    [IEV number 151-15-28]
    [IEV number 442-01-20]

    FR

    surintensité, f
    courant électrique supérieur au courant électrique assigné
    NOTE – Pour des conducteurs, on considère que le courant assigné est égal au courant admissible.
    [IEV number 826-11-14]


    surintensité
    courant supérieur au courant assigné
    [IEC 61095, ed. 2.0 (2009-02)]
    [IEV number 442-01-20]
    surintensité, f
    courant électrique dont la valeur dépasse une valeur limite spécifiée
    [IEV number 151-15-28]

    Параллельные тексты EN-RU

    The design of LV installations leads to basic protection devices being fitted for three types of faults:

    • overloads
    • short-circuits
    • insulation faults
    [Schneider Electric]

    Низковольтные электроустановки должны быть оснащены устройствами защиты трех типов:

    • от перегрузки;
    • от короткого замыкания;
    • от токов утечки.

    [Перевод Интент]

    Примечание
    .
    Слово fault в данном случае пришлось опустить, поскольку:
    - его нельзя перевести как "неисправность", т. к. возникновение 
    перегрузки ( overload) не является неисправностью;
    - его нельзя перевести как "сверхток", т. к. ток утечки не является сверхтоком
    .

    The chosen switchgear must withstand and eliminate faults at optimised cost with respect to the necessary performance.
    [Schneider Electric]

    Выбранная аппаратура распределения должна иметь такие характеристики, чтобы рентабельно выдерживать и ограничивать сверхтоки.
    [Перевод Интент]

     

    Тематики

    Синонимы

    EN

    DE

    FR

    Русско-французский словарь нормативно-технической терминологии > сверхток

См. также в других словарях:

  • длительный допустимый ток — (длительный) допустимый ток Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме …   Справочник технического переводчика

  • ( длительный ) допустимый ток — ((continuous) current carrying capacity ampacity (US)): Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их… …   Словарь-справочник терминов нормативно-технической документации

  • длительный ) допустимый ток — ((continuous) current carrying capacity ampacity (US)): Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их… …   Словарь-справочник терминов нормативно-технической документации

  • допустимый длительный ток кабеля (провода) — [Интент] допустимый длительный ток (проводника) Максимальный электрический ток, который проводник способен проводить в продолжительном режиме без превышения его установившейся температурой определённого значения. Допустимый длительный ток… …   Справочник технического переводчика

  • Допустимый длительный ток — (проводника) ток, который может длительно протекать по проводнику, причем установившаяся температура проводника не должна превышать заданное значение при определенных условиях …   Российская энциклопедия по охране труда

  • допустимый длительный ток (проводника) — 3.2 допустимый длительный ток (проводника): По ГОСТ Р 50571.1. Источник: ГОСТ Р 53311 2009: Покрытия кабельные огнезащитные. Методы определения огнезащитной эффективности …   Словарь-справочник терминов нормативно-технической документации

  • Допустимый длительный ток (проводника) — English: Admittion duration current Ток, который может длительно протекать по проводнику, причем установившаяся температура проводника не должна превышать заданное значение при определенных условиях. Примечание. Для проводников допустимый… …   Строительный словарь

  • допустимый длительный ток в движении — 3.5 допустимый длительный ток в движении: Наибольший ток, протекающий через токоприемник при движении в течение 20 мин, при котором нагревы элементов токоприемника не превышают допустимых температур. Источник: ГОСТ Р 54334 2011: Токоприемники… …   Словарь-справочник терминов нормативно-технической документации

  • допустимый длительный ток на стоянке — 3.6 допустимый длительный ток на стоянке: Наибольший ток, протекающий через токоприемник на стоянке в течение 20 мин, при котором нагревы элементов токоприемника и контактного провода не превышают допустимых температур. Источник: ГОСТ Р 54334… …   Словарь-справочник терминов нормативно-технической документации

  • допустимый длительный ток для кабеля — 3.5 допустимый длительный ток для кабеля : По ГОСТ 50571.1. Источник …   Словарь-справочник терминов нормативно-технической документации

  • номинальный ток — 3.18 номинальный ток (rated current): Ток, установленный для выключателя изготовителем. Источник: ГОСТ Р 51324.1 2005: Выключатели для бы …   Словарь-справочник терминов нормативно-технической документации

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»